LM-10C
Product function
LM-10C glacial coolant is a heat transfer medium with good thermal stability. It has excellent low-temperature fluidity, and is widely used in pharmaceutical industry, chemical industry and other fields.
Product composition
The LM-10C glacier coolant is composed of modified hydrocarbons.
Main parameters
LM-10C glacial coolant is a light color liquid and mainly suitable for heating/cooling in a wide temperature range. The operation temperature of LM-10C glacial coolant is -80°C~190°C. LM-10C glacial coolant is recommended to use in closed cycle system.
Typical Properties*
Property | Unit | Value |
Density (20°C) | g/cm3 | 0.76±0.02 |
Average boiling point | °C | 200 |
Pour point | °C | <-100 |
Flash point | °C | >70 |
Kinematic viscosity (40 °C) | mm2/s | 1.3 |
*Not to be construed as specifications.
Physical parameters at different temperatures (reference values)*
Temperature (°C) | 20 | -30 | -50 | -70 | -80 |
Kinematic viscosity (mm2/s) | 1.65 | 6.40 | 15.1 | 56.4 | 285 |
Specific heat (kJ/kg·K) | 2.09 | 1.90 | 1.82 | 1.75 | 1.71 |
Thermal conductivity (W/m·K) | 0.110 | 0.117 | 0.120 | 0.122 | 0.124 |
*Not to be construed as specifications.
Product features
The product has the following features:
Good low-temperature performance, wide temperature range for use, and can be used for heating and cooling systems between -80~190°C.
It is NSF HT1 food grade certified and is suitable for heating/cooling systems that occasionally come into contact with food.
It is almost non-corrosive to metal.
Usage method
1. LM-10C should be used alone, and cannot be mixed with other coolants and heat transfer fluids.
2、After confirming that there is no leakage point in the system, clean the system and drain the water. Add glacier coolant solution to the system as soon as possible after drying.
3. It is only used in a closed system. Prevent moisture from entering the system during use.
4. It shall not be directly used to heat or cool chemicals with oxidizing effect. When used for indirect heating in the production process of food or drugs, it should meet the requirements of relevant national food and drug safety standards.
When a fluid swap or wrong concentration fails
Plants that swap in a different fluid without re-checking the model, or over-concentrate a charge, hand themselves a failure: one watched cooling collapse after switching fluids unverified, another couldn't even drive the pump because the concentration was too high. LM-10C removes that risk with a single, defined secondary-refrigerant formulation for closed low-temperature loops. Clean the system, drain the old charge, run LM-10C alone, and the loop is protected from the compatibility surprises mixed or mis-set batches create. Like LM-10B it's a water-free medium, so ice plugs don't appear as long as the circuit stays sealed and dry — one fluid, one predictable behavior, for the life of the system.
Use note: do not mix with other coolants or heat-transfer fluids; closed loop only; keep moisture out.